GI vs Copper Earthing Strip: Sizes, Weight and How to Choose
Navdeesh Kandhari
9 minutes reading
Nov 27, 2026

Earthing strips connect equipment, panels and lightning protection down conductors to the earth electrodes, and link electrodes together into a grid or ring. The strip carries fault current, so its material and size are as important as the electrode itself. This guide compares GI and copper earthing strips and lists common sizes with their weights.
What an earthing strip does
Connects equipment and panel bodies to the earthing system
Links multiple earth pits into a grid or ring earth
Serves as the down conductor in lightning protection systems
Bonds structural steel and metal services to earth
GI earthing strip
GI (galvanised iron) strip is mild steel flat that has been hot dip galvanised with a protective zinc coating. It is the most widely used earthing strip in India because it is economical, strong and easy to install.
Lower cost per metre
Good mechanical strength
Adequate for most residential, commercial and industrial installations
Zinc coating is gradually consumed in aggressive soils, so coating thickness matters
Copper earthing strip
Copper strip conducts electricity roughly six times better than steel, so a smaller section can carry the same fault current. It also resists corrosion better in most soils.
Excellent conductivity and longer service life
Preferred for substations, data centres, hospitals and sensitive electronics
Significantly higher cost
Higher theft risk on exposed runs
Comparison
Type | Carbon (%) | |
|---|---|---|
Conductivity | Lower | About 6 times higher than steel |
Corrosion resistance | Good while the zinc lasts | Very good in most soils |
Section needed for same current | Larger | Smaller |
Cost | Lower | Higher |
Typical use | General installations, LPS down conductors | Critical installations, substations |
Common sizes and weight per metre
Sizes are given as width x thickness in mm. Weights are for bare strip; galvanising adds a small amount.
GI strip size (mm) | Approx. weight (kg/m) | Copper strip size (mm) | Approx. weight (kg/m) |
|---|---|---|---|
25 x 3 | 0.589 | 25 x 3 | 0.670 |
25 x 5 | 0.981 | 25 x 6 | 1.340 |
32 x 6 | 1.507 | 32 x 6 | 1.715 |
40 x 5 | 1.570 | 50 x 6 | 2.679 |
50 x 6 | 2.355 | ||
50 x 10 | 3.925 |
Formula: weight (kg/m) = width x thickness x 0.00785 for steel, or x 0.00893 for copper.
How to choose the right size
Strip size is decided by the prospective fault current and how long it lasts before the protection clears it. IS 3043 gives the method for calculating the minimum cross-section. In practice, 25 x 3 mm GI is common for small installations, with 25 x 5, 32 x 6 and 50 x 6 mm used as fault levels rise. Always follow the designer's calculation for your project.
Installation tips
Bury strip at a consistent depth, commonly around 0.5 to 0.6 m, below the frost and digging line
Overlap joints and bolt or weld them; protect welded GI joints with zinc-rich paint
Use exothermic welding for copper joints where possible
Never join copper and GI directly: use bimetallic connectors to prevent galvanic corrosion
Provide test points so each section can be checked
What to check in GI strip
The value of GI strip lies in its zinc coating. Ask for hot dip galvanised strip rather than electro galvanised, which has a much thinner coating. Check that the coating is continuous and smooth, without bare patches, flaking or heavy lumps, and that the size and thickness match the order. Store strip off the ground and under cover until it is installed, because wet storage can cause white rust on the zinc surface.
Earthing strip in lightning protection
In a lightning protection system, earthing strip is used both as the down conductor running down the building and as the ring earth that links the earth pits at ground level. Down conductors should run as straight and short as possible, without sharp bends, and each one should have a test joint above ground so the earth termination can be tested separately. The same strip quality and jointing rules apply as for power system earthing.
Frequently asked questions
Which GI strip size is used for earthing?
25 x 3 mm is common for small installations, with 25 x 5, 32 x 6 and 50 x 6 mm used for higher fault levels. The correct size comes from the fault current calculation in IS 3043.
What is the weight of a 25 x 3 GI strip per metre?
About 0.59 kg per metre before galvanising, slightly more after.
Can copper and GI earthing strips be joined together?
Not directly. Copper and zinc-coated steel in contact cause galvanic corrosion. Use a bimetallic connector between them.
Which is better for earthing, GI or copper strip?
Copper has better conductivity and corrosion resistance and lasts longer, but costs much more. GI is the practical choice for most installations, while copper is preferred for substations and critical facilities.
Need earthing strip for a project? Tell us the size, length and quantity. Send your requirement on WhatsApp: +91 7065337337, or browse the range on ssengineeringwork.in.